Outdoor Enclosure Part Number: 048-678-10
|
 |
 |
- Dual compartment design provides operational cost savings using a heat exchanger to cool equipment in the sealed upper compartment and ambient cooling for batteries in the vented lower compartment
- 13RU of rack space in the top section provides room for rectifiers, distribution, main radio units, surge protection and other 23” rack mountable equipment
- 72” tall, 30” wide and 30” deep provides a compact overall footprint that can easily be used in new site builds or existing equipment lineups
- Compliant with GR-487, the enclosure is designed for high reliability and long operating life in extreme environments
- 3 battery trays provide room for 6 strings of 24Vdc or 3 strings of -48Vdc batteries each rated at 150Ahrs or more
Alpha outdoor enclosures bring versatility and reliability to outdoor power system enclosures. The Te45v2 Outdoor Power Enclosure is a 72" tall enclosure designed to provide -48Vdc power to various telecom equipment.
Welded aluminum construction provides structural integrity that will withstand seismic events and harsh weather conditions. The Te45v2 is designed with the flexibility to house equipment from various vendors and to expand as powering needs change.
Trust Alpha outdoor enclosures to provide the ultimate protection for network equipment.
|
| |
|
| Mechanical Specifications |
| Dimensions (mm): |
1829H x 762W x 762D |
| Dimensions (in): |
72H x 30W x 30D |
Weight (No Batteries): |
236kg (520lbs) |
| Mounting: |
Pad or platform |
| Cooling: |
Heat exchanger for power compartment Forced air ambient for battery compartment |
| Enclosure: |
Aluminum, 5052-H32 |
| Rack Units: |
23", 11RU (UC) |
| Environmental Specifications |
| Operating Temperature: |
-40 to +46°C (-40 to 115°F) |
| Storage Temperature: |
-40 to +85°C (-40 to +185°F) |
| Humidity: |
0 to 95% non-condensing) |
| Elevations: |
3600 m, see operating temperature (12,000 feet) |
| Weather Tighness: |
NEMA Type 3R |
| Electrical |
| Input Voltage: |
120/240Vac, 60Hz single phase 120Vac for auxiliary equipment 120/240Vac for rectifiers |
| Output Voltage: |
48Vdc or 24Vdc |
| Output Power: |
9.0kW (5x Cordex 48V rectifiers; Alpha #010-580-20) (as shown) |
| |
|
|
|