CXPS-HD 48-1.2-225 Standard 48Vdc Power System Part Number: #0530082-000
|
 |
 |
- Integrated 48V, 225A system package
- Ultra compact, high density (HD) design using the latest mini 1RU circuit breakers
- High efficiency design for reduced operating expenses
- High temperature rated, fan-cooled design for harsh outdoor installations
- Wide range AC input and IEC line cords for multiple AC services
Cordex High-Performance (HP) rectifiers make a proven, reliable platform even better, with significant advancements in efficiency and performance. Featuring a compact, fan-cooled design, HP rectifiers open the possibility to wider ranges of applications and immediate Op-Ex/Cap-Ex savings, reducing total cost of ownership and impact on the environment.
The CXPS-HD 48-1.2-225 is the ideal solution for small to medium 48Vdc applications, providing up to 225 Amps output. With universal 19/23" mounting, high temperature operation, compact 3RU height and 15" depth, it is a perfect solution for a wide variety of installation scenarios including those in harsh, outdoor environments.
The distribution center provides (10) plug-in breaker positions for load distribution, (4) battery breaker positions, integrated shunt and optional low voltage battery disconnect (LVBD). With the shunt positioned to measure battery current, a higher accuracy of battery float current is achieved while the system is able to report load current by calculation.
The modular CXCM1 controller includes a web server, providing easy setup via local or remote IP access, using a standard Windows Internet Explorer browser. The CXCM1 also includes LED indicators and an LCD screen for voltage and current display.
The CXPS-HD 48-1.2-225 can be easily integrated into customer provided relay racks or enclosures or can be ordered factory-installed into various Alpha relay rack configurations, including systems with pre-wired battery trays.
|
 |
|
| Features |
| Configurations: |
|
| 0530082-002: |
225A System with LVBD |
| 0530082-003: |
225A System without LVBD |
| Rectifier: |
Up to 9x 48V-1.2kW rectifier positions |
| Distribution: |
10x load breaker positions (mini breaker, plug-in style) 4x battery breaker positions (mini breaker, plug-in style) 225A Low voltage disconnect option 200A Battery shunt |
| Controller: |
CXCM1 Modular controller (included) |
| Electrical |
| Input: |
|
| Voltage: |
176 to 312Vac (nominal) 90 to 176Vac (de-rated O/P power) |
| Current: |
7.5A max (176 to 300Vac) per module 6.0A max (90 to 176Vac) per module |
| Frequency: |
45 to 66Hz |
| Efficiency: |
>93% (50-100% load @ nominal voltage) |
| Power factor: |
>.99 |
| Output: |
|
| Current: |
|
| System: |
225A max @ 48Vdc (nominal I/P)50A max @ 48Vdc (115Vac) |
| Rectifier: |
25A max @ 48Vdc (nominal I/P) 12.5A max @ 48Vdc (115Vac) (subject to de-rating below 110Vac) |
| Power: |
|
| System: |
10,800W max @ nominal I/P 5400W @ 115Vac I/P |
| Rectifier: |
1200W max @ nominal I/P 600W @ 115Vac (subject to de-rating below 110Vac) |
| Mechanical |
| Dimensions: |
|
| mm: |
133H x 438W x 381D |
| inches: |
5.25H x 17.24W x 15D |
| Weight: |
|
| System: |
21.3kg (47.4lbs) |
| Rectifier: |
2.8kg (6.2lbs) each |
| Mounting: |
19/23" universal mount (center or flush) |
Connnections:
|
|
| Load breaker: |
10x sets, 1/4"-20 studs on 5/8" centers |
| Battery breaker: |
4x sets, 1/4"-20 studs on 5/8" centers |
| Return bar: |
14x sets, 10-32 studs on 5/8" centers |
| Alarm: |
Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG) |
| Access: |
Front access for operation and maintenance |
| Environmental |
| Temperature: |
-40 to 65°C (-40 to 149°F) -40 to 75°C (-40 to 167°F) de-rated output |
| Humidity: |
0 to 95% RH non-condensing |
| Elevation: |
- 500 to 2800m; to 4000m with temperature de-rated to 40°C (-1640 feet to 9186 feet; to 13124 feet with temperature de-rated to 104°F) with de-rated output |
| Related Components |
| 010-619-20-041: |
Cordex CXRF 48-1.2kW Rectifier Module |
| 018-598-20-043: |
Cordex CXCM1 |
| 877-690-19: |
5-15P (120V) Line Cord, 2.5M |
| 877-790-19: |
Universal Line Cord, Flying leads, 3.5M |
| 747-095-20-072: |
Temperature sensor assembly 12 ft, 1/4” lug |
| 747-095-20-075: |
Temperature sensor assembly 12 ft,3/8” lug |
| 747-622-20-000: |
Blank Plate |
|
|
|