48V High Capacity Distributed Power Systems
|
 |
 |
- -48V Distributed Power solution for CO’s, MSC's, Data Center and Cable Headend facilities (DPCO)
- Each 2500A bay combines rectifiers, battery termination and distribution
- Dual bay kit links two 2500A bays doubling capacity, breakers and termination
- High circuit count distribution eliminates BDFB’s and reduces installation costs
- High efficiency modular rectifiers reduce operating costs
- Compact front access design reduces floor space footprint
- Flexible low voltage load or battery disconnect, circuit breaker, TPS and TPL fuse options
The Cordex Distributed Power System provides high capacity DC power for large communication networks applications. This system combines the capabilities of modular distribution, advanced microprocessor based supervision, and modular rectifiers in a single integrated bay. Two bays can easily be linked together and share a central controller to double the system capacity.
The Cordex Distributed Power System is cost effective due to the internal copper buswork, and is delivered ready to assemble with factory tested components. No overhead bus work is required. An optional external return bus is available. Cable access is from the top and load connections from the front. Hot swappable Cordex power modules and internal buswork provide safe and easy installation and maintenance.
|
 |
|
| Features |
| Electrical |
| Rectifier shelf AC input: |
Single Phase, 208 to 277Vac Dual 3 Phase, 208 to 240Vac (w/o neutral) Dual 3 Phase, 360 to 480Vac (with neutral) |
| Rectifier Voltage: |
208 to 277Vac |
| Max. output Power: |
120kW One bay system 240kW Two bay system |
| Max. bus capacity: |
2,500A One bay system 5,000A Two bay system |
| Mechanical |
| Dimensions(one bay): |
|
| mm: |
2133H x 660W x 482D |
| inches: |
84H x 26W x 19D |
| Weight: |
|
| System: |
227kg (500lbs) approx |
| Rectifier: |
8.5kg (19lbs) each |
| Mounting: |
Standard center mount 23" relay rack |
| Environmental |
| Temperature: |
0 to 50°C (32 to 122°F) |
| Humidity: |
0 to 95% RH non-condensing |
| Elevation: |
-500 to 2800m (-1640 to 9186ft) |
|
|
|