Standard 48Vdc Power System Part Number: 053-991-20
|
 |
 |
- 48Vdc systems using high density 1.8kW rectifiers
- Front access DC connections
- Integrated CXCM2 modular digital controller
- Wide range AC input
- Optional integrated systems with battery trays
- Integrated system shunt and LVD
Alpha CXPS standard power systems bring proven Cordex technology into a standard integrated system package. The CXPS 48-1.8-M2 uses high density 48V-1.8kW rectifiers, a front access distribution center, and the advanced, modular CXCM2 controller.
The CXPS 48-1.8-M2 is a perfect solution for various small to medium-sized 48Vdc applications, and with a small footprint and high temperature operation is ideal for outside plant installations. The system provides up to 262 Amps of 48Vdc power, and includes 14 load and 4 battery breaker positions along with a low voltage battery disconnect and shunt.
The system is a universal 19" or 23" rack mount design and can be easily integrated into various racks, boxbays, or enclosures. The system can also be ordered factory-installed into various Alpha rack configurations including systems with pre-wired battery trays.
|
 |
|
| Electrical |
| Input: |
|
| Voltage: |
176 to 312Vac (nominal) 90 to 176Vac (de-rated O/P power) |
| Current: |
14.6A @ 240Vac (per module) 12.2A @ 120Vac (per module) |
| Frequency: |
45 to 66Hz |
| Efficiency: |
>91% (50-100% load @ nominal voltage) |
| Power factor: |
>.99 |
| Output: |
|
| Current: |
|
| System: |
262.5A max @ nominal I/P 168A max @ 120Vac I/P |
| Rectifier: |
37.5A @ 48Vdc (nominal I/P) 24A @ 48Vdc (115 to 135Vac) (de-rated linearly to 18.75A @ 90Vac) |
| Power: |
|
| System: |
12600W max @ nominal I/P 8050W @ 120VAC I/P |
| Rectifier: |
1800W max @ nominal I/P 1150W (115 to 135Vac) (de-rated linearly to 900W @ 90Vac) |
| Mechanical |
| Dimensions: |
mm: 222H x 438W x 310D inches: 8.75H x 17.24W x 12.2D (-000 configuration - excludes mounting brackets, rear cover, and module handle) |
| Weight: |
System: 28kg (62lb) Rectifier: 2.8kg (6.2lb) each |
| Mounting: |
19/23in universal mount (center or flush) |
| Connnections: |
|
| Load breaker: |
14x sets, ¼in-20 studs on ⅝in centers |
| Battery breaker: |
4x sets, ¼in-20 studs on ⅝in centers |
| Return bar: |
18x sets, ¼in holes on ⅝in centers |
| AC input: |
Box type terminal block, 6 to 16mm2 (10 to 6AWG) |
| Alarm: |
Screw terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG) |
| CXCM2 input: |
3x DB-style cable connections |
| Access: |
Front access after installation |
| Environmental |
| Temperature: |
-40 to +65C (-40 to 149F) -40 to +75C (-40 to 167F) de-rated output |
| Humidity: |
0 to 95% RH non-condensing |
| Elevation: |
-500 to +2800m (-1640 to 9186ft) -500 to +4000m (-1640 to 13124ft) with de-rated output |
|
|
|