48Vdc Cordex 1kW

Cordex 1kW 48Vdc Modular Switched Mode Rectifier
Part Number: 010-566-20
  • Available in 20.8A @ 48Vdc
  • Power limiting and wide range AC input
  • 92% efficiency and power factor correction
  • Convection cooled
  • Hot swappable, 4RU ultra compact design

Cordex rectifiers bring advanced technology to the DC power industry. Innovative engineering combines the best in efficiency and reliability meeting the power requirements for a variety of system applications.

The Cordex 1kW integrated 19in or 23in shelf systems with distribution is ideal for applications with lower power requirements. A compact 4RU design allows five rectifiers plus controller or six rectifiers per 19in shelf for bulk power needs.

Local and remote setup, adjustment and control is a simple, single-step process with the Cordex CXC System Controller. By utilizing TCP/IP technology, complete configuration and monitoring of power equipment is possible through a network web browser.

Electrical
Input voltage:
Nominal: 208 to 277Vac
Operating: 150 to 320Vac
Extended: 150 to 90Vac (de-rated power)
Input frequency: 45 to 66Hz
Power factor: >0.99%
Efficiency: >92%
Power output: 1000W continuous/module
Output voltage: 42 to 60Vdc
Output current: 18.5A @ 54Vdc (20.8A max)
Load regulation: <±0.5% (static)
Line regulation: <±0.1% (static)
Transient response: ±1% for 50 to 100% load step
2ms recovery time
Noise:
Voice band: <32dBrnC
Wide band: <5mVrms <100mV p -p
Psophometric noise: <1mV
Mechanical
Dimensions: mm: 177H x 71W x 250D
inches: 6.9H x 2.8W x 9.8D
Weight: 2.9kg (6.4lb)
Environmental
Temperature:
Operation: -40 to 50C (-40 to 122F) (with short periods up to 70C/158F)
Storage: -40 to 85C (-40 to 185F)
Humidity: 0 to 95% RH non-condensing
Elevation: -500 to 4000m (-1640 to 13120ft)
Heat dissipation: <295BTU per hour