48V Modular Inverter System
|
 |
 |
- Versatile modular design provides flexibility for different power applications
- Expandable capacity up to 18KVA with N+1 redundancy configuration
- All master in dynamic mechanism eliminates single point failure to optimize reliability
- Hot swappable operation allows module addition or removal without powering down
- High power density and high efficiency
The INEX inverter series is an integrated telecommunications power system, including inverter, static switch, LCD display controller, and interface modules. With a versatile “building blockin design and N+1 redundant configuration, the INEX inverter system satisfies complex telecommunications and industrial power demands, and provides ultimate flexibility for your current and future power requirements.
N+1 parallel redundancy allows power capacity expandable up to 18KVA. INEX all masterin dynamic mechanism automatically shares and re-organizes critical loads to prevent interruption should any inverter module fail. The DSP-microprocessing controller gives real-time system status through a comprehensive LCD display, and allows programmable settings through the display panel. With a communication interface module installed, you can further control and monitor the system remotely.
|
 |
|
| Electrical |
| Inverter Module |
|
| DC input: |
|
| Nominal voltage: |
48Vdc |
| Operating range: |
40.5Vdc ~ 58Vdc |
| Input protection: |
Reverse polarity protection |
Psophometric noise voltage: |
≤1.0mV ITU-T O.41 (16.66~6000Hz) |
| AC output: |
|
| Power rating: |
1500VA/1200W |
| Waveform: |
Pure sine wave |
| Power factor: |
0.8 |
| Nominal output voltage: |
110/115/120Vac, 208/220/230/240Vac |
| Voltage variation: |
Max ±2% |
| Output frequency: |
50/60Hz |
| Crest factor: |
3:1 |
| THD: |
<3%, linear load <5%, non-linear load |
| Efficiency: |
Min 88% |
| Isolation AC-enclosure: |
Basic isolation (Pri-Gnd) 2121Vdc/1min |
| Dynamic response: |
<±10% |
| Over load protection: |
1.5*Inom >20s 1.25*Inom temperature controlled |
| STS Module |
|
| Input: |
|
| Over voltage threshold: |
Adjustable between 127 to 138Vac for 120Vac systems, the default value is 132Vac 233 to 252Vac for 220Vac systems, the default value is 242Vac |
| Under voltage threshold: |
Adjustable between 100 to 114Vac for 120Vac systems, the default value is 108Vac 176 to 209Vac for 220Vac systems, the default value is 198Vac |
| Backfeed protection: |
Comply with safety requirement |
| Redundant power: |
Startup power-on by priority |
| Design: |
Source or alternative |
| Output: |
|
| Nominal output voltage: |
Same as utility or the output of inverter modules |
| Permissible frequency area: |
Max. +/-2.5% (inverter synchronization) |
| Transfer time: |
Typical ¼ cycle |
| Rated power: |
50A for 110/115/120Vac & 208/220/230/240Vac |
| Operation methods: |
Inverter priority/mains priority |
| Mechanical |
| Inverter Module |
|
| Dimensions: |
mm: 270D x 215W x 43.8H inches: 10.63D x 8.46W x 1.72H |
| Weight: |
2.5kg (5.5lb) |
| STS Module |
|
| Dimensions: |
mm: 270D x 215W x 43.8H inches: 10.63D x 8.46W x 1.72H |
| Weight: |
2.0kg (4.4lb) |
| Controller Module |
|
| Dimensions: |
mm: 277D x 87.9W x 43.5H inches: 10.9D x 3.46W x 1.71H |
| Weight: |
1.0kg (2.2lb) |
| Hot-swap Chassis |
|
| 19/23in mounting brackets |
| Inverter chassis |
|
| Dimensions: |
mm: 329.5D x 440W x 44H inches: 13D x 17.32W x 1.73H |
| Weight: |
2.5kg (5.5lb) |
| STS & controller chassis |
|
| Dimensions: |
mm: 329.5D x 440W x 44H inches: 13D x 17.32W x 1.73H |
| Weight: |
3.4kg (7.5lb) |
| Environmental |
| Operating temperature: |
-20 to 70C (-4 to 158F) -5 to 58C (23 to 122F) with full performance |
| Storage temperature: |
-40 to +85C (-40 to 185F) |
| Humidity: |
90% RH non-condensing |
| Audible noise: |
55dB |
|
|
|