AlphaCell 85 GXL-HP

Gel Top Terminal Batteries
AlphaCell 85 GXL-HP
  • Designed specifi cally for standby applications
  • Deliver 100% “out-of-box” capacity — no cycling required
  • Premium Gel model offers 50% longer life than traditional gel batteries
  • Full replacement, non-prorated warranties
  • Silver Alloy minimizes grid corrosion
  • Maintenance-free threaded inserts; no periodic retorquing

Alpha’s standby battery offering incorporates true Gel Cell and Silver Alloy grid battery technologies, ensuring optimal performance for your outdoor cable, traffi c or WiFi application. AlphaCell batteries provide the ultimate warranty, longest runtimes and superior longevity in today’s demanding outdoor non-temperature controlled cable power environments.

Due to the implementation of the HST and the elimination of the provincial sales tax in British Columbia, Canada, the $5 battery levy will be eliminated effective July 1, 2010. The BC Government will continue to fund the programs to offset the revenue loss and will review the Sustainable Environment Fund (SEF) budget annually.

 
General Specifications
Warranty: 5 year, full replacement
Service Life: Extended
Runtime (minutes): 85
Sealed VRLA: Valve Regulated Lead Acid
Heat Resistant: Extreme
Hydrogen Emission: Low
Terminals: Threaded insert 10 - 32 UNF
Cells Per Unit: 6
Voltage Per Unit: 12.8
Conductance Value: 600
Max. Discharge Current (A): 600
Short Circuit Current (A): 2200
10 Second Volts @ 100A: 10.8
Ohms Impedance 60Hz: 0.0065
Capacity at 20hrs (to 1.75VPC): 50AH
BCI Group Size: 22
Weight (lb/kg): 39.6/18
Dimensions H x W x D (in/mm): 8.1 x 9 x 5.5 / 206 x 228 x 139
 
Operating Temperature Range
Discharge: -40 to 71°C (-40 to 160°F)
Charge (with temp compensation): -23 to 60°C (-9.4 to 140°F)
Float Charging Voltage @ 25°C / 77°F: 13.5 to 13.8Vdc
AC Ripple Charger: 0.5% RMS or 1.5% of float charge voltage recommended for best results.
Max. allowed = 4%V pk to pk
 