Telecommunications
Wireless
UPS
Industrial Power
Service and Support
Cable/Broadband
Renewable Energy
Alpha Catalog
Alpha Webstore
The Alpha Group
The Alpha Group represents an alliance of independent companies who share a common philosophy - to create world class powering solutions.

Collectively, Alpha Group members develop and manufacture AC and DC power conversion protection, and standby products. Applications for these products include broadband, telecom, AC/UPS, commercial, industrial, and distributed generation,
for a worldwide customer base. In addition, our companies provide a range of installation and maintenance services.

Members of The Alpha Group include Alpha Technologies Inc., Alpha Energy, Alpha Industrial Power, Alpha Technologies Ltd. and Altair Advanced Industries Inc.
Share |

AlphaCell 3.5 and 4.0HP

Pure Lead Top Terminal Batteries
alphacell-35-and-40hp
  • Class leading batteries featuring pure lead technology providing up to 20% increased life expectancy
  • 3 to 5 times longer shelf life versus standard VRLA batteries
  • Up to 50% increased runtime in cold climates
  • Non-spillable UN2800 rating for ease of transportation
  • Higher runtime allows string count reduction
  • 5-year full, hassle-free warranty

AlphaCell HP Pure lead AGM batteries provide high power density and extended reliability for broadband applications. AlphaCell batteries enable using fewer strings in power systems compared to standard batteries while maintaining network runtime and reliability. For power supply loads that are less than 8 amps, 4 hours runtime can be achieved using a single string of AlphaCell 4.0 HP batteries, compared to using two strings of competitive products. Additionally, AlphaCell HP batteries provide up to 50% more runtime in colder climates compared to standard batteries.

 

Nominal Specifications

General Specifications
Model: 3.5HP (P/N 1810077) 4.0HP (P/N 1810078)
Warranty: 5 year full replacement
Service Life: Extended
Battery Type: Pure Lead AGM
Heat Resistant: Extreme
Hydrogen Emission: Low
Capacity at 20hrs (to 1.75VPC): 104Ah 114Ah
Typical runtime (minutes)**: 210 240
BCI group size: 31
Terminals: Threaded insert 1/4 - 20 UNC"
Cells Per Unit: 6
Voltage Per Unit: 12.8
Conductance Valve: 1700 2100
Impedance @ 60Hz (Ohms): 2.7 2.2
Max. discharge current (A): 800 900
Short circuit current (A): 2800 3200
10 second volts @ 100A: 11.7 11.8
 
Mechanical
Height w/terminals
mm (inches):
223.5H x 337.8W x 172.7D (8.5H x 13.4W x 6.8D) 223.5H x 337.8W x 172.7D (8.5H x 13.4W x 6.8D)
Weight: 30.8kg (68lbs) 35.6kg (74lbs)
 
Environmental
Discharge: -40 to 60°C (-40 to 140°F) -40 to 60°C (-40 to 140°F)
Charge
(w/temperature compensation):
-40 to 60°C (-9.4 to 140°F) -40 to 60°C (-9.4 to 140°F)
Float charging voltage: 13.5 to 13.8Vdc 13.5 to 13.8Vdc
AC ripple charger: 0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4%V pk to pk

AlphaCell HP current discharge ratings in Amps (end voltage 1.75VPC @ 25ºC/77ºF)

Hours123481020
3.5HP: End voltage 1.75VPC: 70.2 40.3 28.6 22.3 12.1 9.9 5.2
End voltage 1.75VPC: 72.0 41.1 29.2 22.7 12.3 10.0 5.3
4.0HP: End voltage 1.75VPC: 81.9 45.8 32.2 25.0 13.1 10.6 5.7
End voltage 1.75VPC: 83.7 46.7 32.8 25.4 13.3 10.7 5.8

AlphaCell HP Amp hour ratings in Amps (end voltage 1.75VPC @ 25ºC/77ºF)

Hours123481020
3.5HP: End voltage 1.75VPC: 70.2 80.6 85.8 89.2 96.8 99 104
End voltage 1.75VPC: 72.0 82.2 87.6 90.8 98.4 100 106
4.0HP: End voltage 1.75VPC: 81.9 91.6 96.6 100 104.8 106 114
End voltage 1.75VPC: 83.7 93.3 98.3 101.5 106.3 107 115.8
Request Quote

Share