AlphaCell™ 195 GXL-FT

Gel Front Terminal Batteries
AlphaCell 195 GXL-FT
  • Front terminals with protective covers
  • Valve regulated lead acid batteries
  • Long life gel batteries can be used outdoors
  • Ideal for telecom and cable applications

Due to the implementation of the HST and the elimination of the provincial sales tax in British Columbia, Canada, the $5 battery levy will be eliminated effective July 1, 2010. The BC Government will continue to fund the programs to offset the revenue loss and will review the Sustainable Environment Fund (SEF) budget annually.

 
Nominal Specifications
Service life: Extended
Sealed VRLA: Valve regulated lead acid
Heat resistant: Extreme
Hydrogen emission: Low
Terminals: 16mm insert M6 thread
Typical runtime: 195 mins
Cells per unit: 6
Voltage per unit: 12.8
Conductance value: 1200
Max. discharge current: 400A
Short circuit current: 3000A
10 Second volts @ 100A: 10.8
Impedance @ 60Hz (Ohms): 0.0041
Capacity at 20hrs (to 1.75VPC): 110Ah
 
Mechanical
Dimensions w/ terminals*: mm: 285H x 110W x 395D
inches: 11.22 x 4.33W x 15.55D
Weight: 34.52kg (76.29lb)
 
Environmental
Discharge: -40 to 71°C (-40 to 160°F)
Charge (with temp compensation): -20 to 50°C (-4 to 122°F)
Float charging voltage (Vdc) Float 2.27 to 2.30VPC @ 25°C cycling 2.35VPC @ 25°C
AC ripple charger 0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4% P-P
*Dimensions at top of battery. For information on the warranties please contact your sales rep.
Current Discharge Ratings Table in Amps (End Voltage 1.75VPC)
Hours 1 2 3 4 6 8 10 12 20 24 48 72 100
195 GXL-FT 71.1 38.0 26.8 21.1 15.2 12.0 9.92 8.48 5.50 4.60 2.31 1.56 1.13

Request Quote

Share