EnergyCell RE Front Terminal

Front Terminal Renewable Energy Batteries
  • Product Line: Batteries
  • Related Categories: Batteries
EnergyCell RE Front Terminal
  • Front terminal access design for ease of maintenance and installationapplications
  • High-density pasted plates for high cycle life
  • Lead-calcium-tin alloy plates for long life in both cycling and float applications
  • High recharge efficiency
  • Compact footprint for higher density energy requirements
  • Thermally welded case-to-cover eliminates leakage
  • UL-recognized component
  • Description

    The EnergyCell RE Valve Regulated Lead Acid (VRLA) battery is designed for high power density and renewable energy cycling applications. Absorbed Glass Matt (AGM) technology provides efficient gas recombination of up to 99% and freedom from electrolyte maintenance. The EnergyCell RE also features low profile terminals with threaded copper alloy inserts providing reduced maintenance and increased safety.

    • Nominal Specifications
      Model EnergyCell 170RE EnergyCell 200RE
      P/N 1810255 1810137
      Warranty¹ 2 years 2 years
      Voltage Per Unit 12 Vdc Unit 12 Vdc
      Self Discharge Battery can be stored up to 18 months at 25°C (77°F) before a freshening charge is required. Batteries stored at temperatures greater than 25°C (77°F) will require recharge sooner than batteries stored at lower temperatures.
      Temp Compensation Factor (Charging) ±5mV per °C per cell (2V)
      Terminal Threaded copper alloy insert terminal to accept ¼"-20 UNC bolt
      Terminal Hardware Initial Torque 110 in-lbs (12.4 Nm)
      Mechanical
      Dimensions mm 283H x 559D x 126W 320H x 5509D x 126W
      Dimensions inches 11.14H x 22.01D x 4.95W 12.60H x 22.01D x 4.95W
      Weight 52kg (115lbs) 60kg (131lbs)
      * Batteries to be installed with 0.5in (12.7mm) spacing minimum and free air ventilation
      Environmental
      Operating Temperature Range (with temperature compensation) Discharge: -40 to 71°C (-40 to 160°F) Charge: -23 to 60°C (-10 to 140°F)
      Optimal Operating Temp Range 23 to 27°C (74 to 80°F)
      Recommended Maximum Charging Current Limit Per String 25 Amps DC
      Float Charging Voltage 13.62 Vdc/unit average at 25°C (77°F)
      Equalization and Cycle Service Charging Limits 14.4 Vdc/unit average at 25°C (77°F)
      Current Discharge Ratings Table in Amps (End Voltage 1.75VPC @ 25°C/77°)
      Hours 1 3 4 5 8 12 20 24 48 100
      EnergyCell 170RE 89.1 38 30.15 25.18 17.12 12.10 7.69 6.54 3.41 1.7
      EnergyCell 200RE 103 44 34.9 29.1 19.8 14 8.9 7.55 3.95 2

      1. Warranty in US/Canada only for other regions consult your salesperson for details.