AlphaCell GXL

Gel Top Terminal Batteries
  • Product Line: Batteries
  • Related Categories: Batteries
AlphaCell GXL
  • High-performance silver alloy battery for maximum life expectancy
  • Longer runtime for demanding outdoor environments
  • 100% runtime capacity out-of-box – no cycling required
  • Maintenance-free threaded inserts – no periodic retorquing
  • Available with 4 and 5 year full warranties*
  • Wide operating temperature range

  • Buy Now

    Description

    Alpha’s standby battery offering incorporates Gel for thermal dissipation to ensure optimal life performance for your particular Broadband, Traffic or Wi-Fi application. AlphaCell Batteries provide the longest runtimes and the best longevity in today’s demanding outdoor applications and are backed by Alpha’s industry leading, non-prorated warranties.

    * Warranty varies by country and region. Warranty valid only when used with Alpha approved power supplies, chargers and enclosures in US/Canada. 5 years warranty when purchased in conjunction with AlphaGuard. Consult your salesperson or manual for details.
    ** Runtime calculated using a 25A DC constant current load

    • Nominal Specifications for Gold-HP
      Model: 220 GXL 195 GXL 165 GXL 85GXL-HP
      P/N: 181-231-10 181-230-10 1810015 181-213-10
      Warranty: 4 to 5 years full replacement
      Service Life: Extended
      Battery Type: True gel cell and silver alloy grid battery technologies
      Heat Resistant: Extreme
      Hydrogen Emission Low
      Capacity at 20hrs (to 1.75VPC) 109Ah 100Ah 86Ah 50Ah
      Typical Runtime (minutes)**: 221 196 165 85
      BCI Group Size: 31 31 27 22
      Terminals: Threaded insert 1/4 to 20 UNC Threaded insert 10-32 UNF
      Cells Per Unit 6 6 6 6
      Voltage Per Unit 12.8V 12.8V 12.8V 12.8V
      Conductance Value @ 25°C
      910-1400 880-1320 800-1200 480-720
      Impedance @ 60Hz (Ohms) 0.005 0.005 0.0055 0.0065
      Max. Discharge Current 900A 900A 800A 600A
      Short Circuit Current 2800A 2600A 2500A 2200A
      10 Second Volts @ 100A 11.4 11.3 11.2 10.8
      Mechanical
      Dimensions (Height includes terminals)        
          mm: 215.4H x 340.9W x 172.7D 215.4H x 340.9W x 172.7D 204.5H x 317.8W x 173.4D 206H x 228W x 139D
          inches: 8.48H x 13.4W x 6.8D 8.5H x 13.4W x 6.8D 8.5H x 12.5W x 6.83D 8.1H x 9W x 5.5D
      Weight: 33.2kg (73lbs) 30.5kg (67lbs) 30.5kg (67lbs) 18kg (39.6lbs)
      Environmental (All Models)
      Discharge: -40 to 71°C (-40 to 160°F)
      Charge (with temperature compensation) -5mV/C per °C -23 to 60°C (-9.4 to 140°F)
      Float Charging Voltage 13.5 to 13.8Vdc
      AC Ripple Charger 0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4%V pk to pk
       
      AlphaCell GXL current discharge ratings in Amps (end voltage 1.75VPC @ 25°C/77°F)
      Hours 1 2 3 4 6 8 10 12 20 24 48 72 100
      220GXL 67.7 40.4 29.1 22.9 16.1 12.6 10.2 8.7 5.5 4.6 2.4 1.6 1.2
      195GXL 65.1 37.4 26.8 21 14.8 11.5 9.5 8 5 4.3 2.2 1.5 1.1
      165GXL 55.9 32.8 23.5 18.4 12.9 10 8.2 6.9 4.3 3.7 1.9 1.3 0.9
      85GXL 33.2 18.8 13.3 10.4 7.34 5.70 4.68 3.97 2.50 2.12 1.11 0.76 0.56
       
    We are experiencing a website download issue that is intermittent, and related to our hosting provider. If something goes wrong with your download, please notify the Alpha team and tell us what document you were looking for. In Canada/USA call (Toll Free): 1-888-462-7487 or International: 1-604-436-5547 or go to www.alpha.ca/report-a-problem